5-22
<Toc> < 5. Parameters >
IM 05D01C02-41E 3rd Edition: May 31, 2006-00
● Output-related Parameters
Located in: Main menu =
(UTMD)
; Submenu =
(OUT)
Parameter
Symbol
Name of Parameter Setting Range and Description Initial
Value
User
Setting
Target Item
in CD-ROM
0
Heating/
cooling
type : 4
(OT1)
(CT)
(CTc)
(AO1)
(AO2)
(AO3)
(A1H)
(A1L)
Time proportional PID relay contact output (terminals - - )
Time proportional PID voltage pulse output (terminals - )
Current output (terminals - )
ON/OFF control relay contact output (terminals - - )
0
1
2
3
4
5
6
7
8
9
10
11
12
Analog output-1 type
(OUTPUT 1:
Terminals and )
Analog output-3 type
(OUTPUT 3:
Terminals and )
0
0
Allows control output or retransmission output to be presented
as one of the following current signals.
0: 4 to 20 mA
1: 0 to 20 mA
2: 20 to 4 mA
3: 20 to 0 mA
0
Analog output-1 100%
segmental
point
Analog output-1 0%
segmental
point
100.0 %Set the values of segmental points for the 0% and 100% output
levels at which the values are presented via OUTPUT-1
(terminals and ). See “■ Performing Split Computations” below.
-5.0% to 105.0%
0.0 %
Analog output-2 type
(OUTPUT 2:
Terminals and )
Relay’s Behavior when Cycle Time = 10 sec.
10 sec.
On-state duration: 5 sec.
Off-state duration: 5 sec.
On-state duration: 8 sec.
Off-state duration: 2 sec.
1 2 3
1 2 3
1 2 3
16 17
16 17
14 15
46 47
Control output
type
The following 4 to 12 are displayed only for heating/ cooling
type controllers.
Heating-side relay output (terminals - - ), cooling-side
relay output (terminals - - )
1 2 3
Heating-side pulse output (terminals - ), cooling-side relay
output (terminals - - )
Heating-side current output (terminals - ), cooling-side
relay output (terminals - - )
Heating-side relay output (terminals - - ), cooling-side
pulse output (terminals - )
Heating-side pulse output (terminals - ), cooling-side pulse
output (terminals - )
Heating-side current output (terminals - ), cooling-side
pulse output (terminals - )
Heating-side relay output (terminals - - ), cooling-side
current output (terminals - )
Heating-side pulse output (terminals - ), cooling-side
current output (terminals - )
Heating-side current output (terminals - ), cooling-side
current output (terminals - )
Control output cycle
time
Heating-side control
output cycle time in
heating/cooling
control
Cooling-side control
output cycle time
1 to 1000
sec. 30 sec.
1 to 1000
sec. 30 sec.
On
Off
On
Off
Cycle time Cycle time
For 20% of Control Output For 50% of Control Output For 80% of Control Output
Off-state duration: 8 sec.
On-state duration: 2 sec.
10 sec.10 sec.
16 17
16 17
16 17
16 17
16 17
48 49 50
48 49 50
48 49 50
46 47
1 2 3
46 47
46 47
16 17
46 47
16 17
46 47
16 17
46 47
Ref.3.3(4)
Ref.2.1(7)
Same as
above
Same as
above
Same as
above
Same as
above
Same as
above