Monitoring and Control of
Regular Operations
Monitoring and Control of Regular Operations (Operation Display)
Table 5.2
No. in
Figure
Name Description
(14) Engineering units Engineering units (UNIT) are displayed in a maximum of seven digits.
(15) PV bar scale The PV bar scale is displayed divided into a maximum of 10 segments (10% segments).
(16)
0% value of scale, 100%
value of scale
0% value of scale (SCL) and 100% value of scale (SCH) are displayed in engineering units in
a digital value of five significant digits (seven digits including a sign and decimal point).
(17)
Alarm generation display,
Control status display
Alarm and control statuses are displayed in abbreviations. These vary according to
controller mode in the multi-function mode; or according to the control module in the
programmable mode. See Tables 5.3 to 5.5.
(18)
P-register display
When this display is enabled, P register is displayed on the LOOP 1 and LOOP 2
Displays individually. This display is available in the programmable mode.
(19)
Operation status display
The controller operation status is displayed.
Display Description
Display
Priority Order
[POWER DOWN] Power down is being detected. (1)
[H.MAN] Hard manual selector switch has been activated. (2)
(No indication) The instrument is operating.
(3)
[STOP] Operation stopped (such as while setting a
function on the Engineering Display, etc.)
[TEST1]
Test run mode 1 (only in the programmable mode)
[TEST2]
Test run mode 2 (only in the programmable mode)
Simulation program is being executed
(20)
Cascade setting input
value
When the instrument is used in the cascade mode, a cascade setting input value is
displayed in engineering units in a digital value of five significant digits (seven digits
including a sign and decimal point). No value is displayed in the programmable mode.
(21)
key function display
The key function is displayed. The key function display is different in the multi-
function mode and the programmable mode.
1) Multi-function mode
The key function is set using the PF key function selection parameter [PFKEY].
When the STC mode selection is “not OFF” and the “ key has been set to STC”,
the function display becomes [STC]. In other cases, nothing is displayed.
2) Programmable mode
The key function can be defined in user programs.
The function display becomes [PF] in the programmable mode.
(22)
Key LOCK status display
The key LOCK status is displayed.
Display Description
[ALLK]
, , and keys, SV increase and decrease ( , ) keys, MV
increase and decrease ( , ) keys, and key are disabled.
[MDLK]
, , and keys are disabled.
[SVLK]
SV increase and decrease (
, ) keys are disabled.
[MVLK]
MV increase and decrease (
, ) keys are disabled.
Table 5.3 Alarm Display and Control Status Display in the YS1500/YS1700 Multi-function Mode
Controller Mode
Display Item
Single Loop Cascade Selector
Alarm generation display (Note 1)
SYS-ALM
STC-ALM
ALARM-1
SYS-ALM
STC-ALM
ALARM-1
ALARM-2
SYS-ALM
STC-ALM
ALARM-1
ALARM-2
Control status display (Note 2)
CAS
SPC, DDC
BUA, BUM
CAS
SPC, DDC
BUA, BUM
CAS
SPC, DDC
BUA, BUM
Control substatus display 1
EXT-MAN,EXT-AUT
EXT-PMV,EXT-TRK
EXT-TRK,EXT-PMV EXT-TRK,EXT-PMV
Control substatus display 2
SV TRK, PV TRK OPEN, CLOSE
SV2-RMT, SV2-LCL
SEL1, SEL2
Control substatus display 3
STC-ON, STC-DSP,
ATSTUP
STC-ON, STC-DSP,
ATSTUP
STC-ON, STC-DSP
Note 1: This display appears only if an alarm occurs. If multiple alarms occur simultaneously, they are indicated in multiple lines.
Note 2: Only when the operation mode is in cascade setting automatic control (C mode) is a control status displayed, while nothing is indicated in
automatic control (A mode) or manual control (M mode).