108 Parameters
05
05 Diagnostics
Various run-time-type counters and measurements related to
drive maintenance.
All parameters in this group are read-only unless otherwise
noted.
05.01 On-time counter On-time counter. The counter runs when the drive is
powered.
-
0…65535 d On-time counter. 1 = 1 d
05.02 Run-time counter Motor run-time counter in full days. The counter runs when
the inverter modulates.
-
0…65535 d Motor run-time counter. 1 = 1 d
05.03 Hours run Corresponding parameter to 05.02 Run-time counter in
hours, that is, 24 * 05.02 value + fractional part of a day.
-
0.0
429496729.5 h
Hours. 10 = 1 h
05.04 Fan on-time
counter
Running time of the drive cooling fan. Can be reset from the
control panel by keeping Reset down for over 3 seconds.
-
0…65535 d Cooling fan run-time counter. 1 = 1 d
05.10 Control board
temperature
Measured temperature of the control board -
-100… 300 °C or °F Control board temperature in degrees Celsius or Fahrenheit. 1 = unit
05.11 Inverter
temperature
Estimated drive temperature in percent of fault limit. The fault
limit varies according to the type of the drive.
0.0% = 0 °C (32 °F)
100.0% = Fault limit
-
-40.0…160.0% Drive temperature in percent. 1 = 1%
No. Name/Value Description Def/FbEq16