46 Program features
Control interfaces
Programmable analog inputs
The control unit has two programmable analog inputs. Each of the inputs can be
independently set as a voltage (0/2…10 V) or current (0/4…20 mA) input with
parameters. Each input can be filtered, inverted and scaled.
Settings
Parameter group 12 Standard AI (page 124).
Programmable analog outputs
The control unit has two current (0…20 mA) analog outputs. Analog output 1 can be
set as a voltage (0/2…10 V) or current (0/4…20 mA) output with a parameter. Analog
output 2 always uses current. Each output can be filtered, inverted and scaled.
Settings
Parameter group 13 Standard AO (page 128).
Programmable digital inputs and outputs
The control unit has six digital inputs.
Digital input DI5 can be used as a frequency input.
Digital input DI6 can used as a thermistor input.
Six digital inputs can be added by using a CHDI-01 115/230 V digital input extension
module and one digital output by using a CMOD-01 multifunction extension module.
Settings
Parameter groups 10 Standard DI, RO (page 117) and 11 Standard DIO, FI, FO (page
122).
Programmable frequency input and output
Digital input DI5 can be configured as a frequency input.
A frequency output can be implemented with a CMOD-01 multifunction extension
module.
Settings
Parameter groups 10 Standard DI, RO (page 117) and 11 Standard DIO, FI, FO (page
122) and 15 I/O extension module (page 133).