Parameters 133
13.28 AO2 source max Defines the real maximum value of the signal (selected by
parameter 13.22 AO2 source) that corresponds to the
maximum required AO2 output value (defined by parameter
13.30 AO2 out at AO2 src max). See parameter 13.27 AO2
source min. See parameter 13.17 AO1 source min about the
AO automatic scaling.
-32768.0…32767.0 Real signal value corresponding to maximum AO2 output
value.
1 = 1
13.29 AO2 out at AO2 src
min
Defines the minimum output value for analog output AO2.
See also drawing at parameter 13.27 AO2 source min.
0.000 mA
0.000 22.000 mA Minimum AO2 output value. 1000 = 1 mA
13.30 AO2 out at AO2 src
max
Defines the maximum output value for analog output AO2.
See also drawing at parameter 13.27 AO2 source min.
20.000 mA
0.000 22.000 mA Maximum AO2 output value. 1000 = 1 mA
13.91 AO1 data storage Storage parameter for controlling analog output AO1 eg.
through the embedded fieldbus interface.
In parameter 13.12 AO1 source, select AO1 data storage.
Then set this parameter as the target of the incoming value
data. With the embedded fieldbus interface, simply set the
target selection parameter of that particular data
(58.10158.114) to AO1 data storage.
0.00
-327.68…327.67 Storage parameter for AO1. 100 = 1
13.92 AO2 data storage Storage parameter for controlling analog output AO2 eg.
through the embedded fieldbus interface.
In parameter 13.22 AO2 source, select AO2 data storage.
Then set this parameter as the target of the incoming value
data. With the embedded fieldbus interface, simply set the
target selection parameter of that particular data
(58.10158.114) to AO2 data storage.
0.00
-327.68…327.67 Storage parameter for AO2. 100 = 1
15
15 I/O extension
module
Configuration of the I/O extension module installed in slot 2.
See also section Programmable I/O extensions (page 47).
Note: The contents of the parameter group vary according to
the selected I/O extension module type.
15.01 Extension module
type
Activates (and specifies the type of) I/O extension module. If
the value is None, when an extension module has been
installed and the dive is powered, the drive automatically sets
the value to the type it has detected (= value of parameter
15.02 Detected extension module); otherwise warning A7AB
Extension I/O configuration failure is generated and you have
to set the value of this parameter manually.
None
None Inactive. 0
CMOD-01 CMOD-01 multifunction extension module (external
24 V AC/DC and digital I/O).
1
CMOD-02 CMOD-02 multifunction extension module (external
24 V AC/DC and isolated PTC interface).
2
CHDI-01 CHDI-01 115/230 V digital input extension module. 3
CPTC-02 CPTC-02 extension module. 4
15.02 Detected extension
module
I/O extension module detected on the drive. None
None Inactive. 0