210 Parameters
37
37 User load curve
Settings for user load curve.
See also section User load curve (Condition monitoring)
(page 52).
37.01 ULC output status
word
Displays the status of the monitored signal. The status is
shown only while the drive is running. (The status word is
independent of the actions and delays selected by
parameters 37.03, 37.04, 37.41 and 37.42.)
This parameter is read-only.
0000h
0000h…FFFFh Status of the monitored signal. 1 = 1
37.02 ULC supervision
signal
Selects the signal to be monitored. The function compares
the absolute value of the signal against the load curve.
Motor
torque %
Not selected No signal selected (monitoring disabled). 0
Motor speed % 01.03 Motor speed % (page 103). 1
Motor current % 01.08 Motor current % of motor nom (page 103). 2
Motor torque % 01.10 Motor torque (page 103). 3
Output power % of
motor nominal
01.15 Output power % of motor nom (page 104). 4
Output power % of
drive nominal
01.16 Output power % of drive nom (page 104). 5
Other Source selection (see Terms and abbreviations on page 100). -
37.03 ULC overload
actions
Selects how the drive reacts if the absolute value of the
monitored signal stays continuously above the overload curve
for longer than the value of 37.41 ULC overload timer.
Disabled
Disabled No action taken. 0
Warning The drive generates a warning (A8BE ULC overload
warning).
1
Fault The drive trips on 8002 ULC overload fault.2
Warning/Fault The drive generates a warning (A8BE ULC overload warning)
if the signal stays continuously above the overload curve for
half of the time defined by parameter 37.41 ULC overload
timer.
The drive trips on
8002 ULC overload fault if the signal stays
continuously above the overload curve for a time defined by
parameter 37.41 ULC overload timer.
3
37.04 ULC underload
actions
Selects how the drive reacts if the absolute value of the
monitored signal stays continuously above the overload curve
for longer than the value of 37.42 ULC underload timer.
Disabled
Disabled No action taken. 0
Warning The drive generates a warning (A8BF ULC underload
warning).
1
Fault The drive trips on 8001 ULC underload fault.2
No. Name/Value Description Def/FbEq16
Bit Name Description
0 Under load limit 1 = Signal lower than the underload curve.
1 Within load range 1 = Signal between the underload and overload curve.
2 Overload limit 1 = Signal higher than the overload curve.
3…15 Reserved