Parameters   273
80.61 Q value Q2 Defines the flow rate at point 2 on the PQ performance curve.
See parameter 80.60 Q value Q1 (page 272).
0.00
80.62 Q value Q3 Defines the flow rate at point 3 on the PQ performance curve.
See parameter 80.60 Q value Q1 (page 272).
0.00
80.63 Q value Q4 Defines the flow rate at point 4 on the PQ performance curve.
See parameter 80.60 Q value Q1 (page 272).
0.00
80.64 Q value Q5 Defines the flow rate at point 5 on the PQ performance curve.
See parameter 80.60 Q value Q1 (page 272).
0.00
81
81 Sensor settings
Defines the sensor settings for inlet and outlet pressure 
protection function.
81.01 Actual inlet 
pressure
Shows the actual inlet pressure.
Note: By default the parameter unit will be bar. However, the 
unit can be changed according to the parameter 81.20 
Pressure unit.
0.00
0.00...32767.00 bar Actual inlet pressure. 1 = 1 bar
81.02 Actual outlet 
pressure
Shows the actual outlet pressure. 0.00
0.00...32767.00 bar Actual outlet pressure. 1 = 1 bar
81.10 Inlet pressure 
source
Selects the primary source used for pump inlet pressure 
measurement.
AI1 scaled
Not selected None 0
AI1 scaled Parameter 12.12 AI1 scaled value.1
AI2 scaled Parameter 12.22 AI2 scaled value.2
Freq in scaled Parameter 11.39 Freq in 1 scaled value.3
AI1 percent Parameter 12.101 AI1 percent value.8
AI2 percent Parameter 12.102 AI2 percent value.9
Feedback storage Parameter 40.91 Feedback data storage.10
Other [bit] Source selection (see Terms and abbreviations on page 100). -
81.11 Outlet pressure 
source
Selects the primary source used for pump outlet pressure 
measurement.
AI2 scaled
Not selected None 0
AI1 scaled Parameter 12.12 AI1 scaled value.1
AI2 scaled Parameter 12.22 AI2 scaled value.2
Freq in scaled Parameter 11.39 Freq in 1 scaled value.3
AI1 percent Parameter 12.101 AI1 percent value.8
AI2 percent Parameter 12.102 AI2 percent value.9
Feedback storage Parameter 40.91 Feedback data storage.10
Other [bit] Source selection (see Terms and abbreviations on page 100). -
81.12 Sensors height 
difference
Defines the height difference between inlet and outlet 
pressure sensors for flow calculation.
0.00
0.00...32767.00 m Sensors height difference. 1 = 1 m
81.20 Pressure unit Selects the unit of pressure. bar
bar Pressure 0
No. Name/Value Description Def/FbEq16