Parameters 287
96.102 User lock
functionality
(Visible when user lock is open)
Selects the actions or functionalities to be prevented by the
user lock. Note that the changes made take effect only when
the user lock is closed. See parameter 96.02 Pass code.
Note: We recommend you select all the actions and
functionalities unless otherwise required by the application.
0000h
0000h…FFFFh Selection of actions to be prevented by user lock. -
97
97 Motor control
Switching frequency; slip gain; voltage reserve; flux braking;
anti-cogging (signal injection); IR compensation.
97.01 Switching
frequency reference
Defines the switching frequency of the drive that is used as
long as the drive stays below the thermal limit. See section
Switching frequency on page 79.
Higher switching frequency results in lower acoustic motor
noise. Lower switching frequency generates less switching
losses and reduce EMC emissions.
Note: If you have a multimotor system, contact your local
ABB representative.
4 kHz
2 kHz 2 kHz. 2
No. Name/Value Description Def/FbEq16
Bit Name Information
0 Disable ABB access
levels
1 = ABB access levels (service, advanced programmer, etc.; see
96.03) disabled
1 Freeze parameter
lock state
1 = Changing the parameter lock state prevented, ie. pass code
358 has no effect
2 Disable file
download
1 = Loading of files to drive prevented. This applies to
• firmware upgrades
• parameter restore
• loading an adaptive program
• changing home view of control panel
• editing drive texts
• editing the favorite parameters list on control panel
• configuration settings made through control panel such as
time/date formats and enabling/disabling clock display.
3…10 Reserved
11 Disable OEM access
level 1
1 = OEM access level 1 disabled
12 Disable OEM access
level 2
1 = OEM access level 2 disabled
13 Disable OEM access
level 3
1 = OEM access level 3 disabled
14…15 Reserved