236 Parameters
45.35 Last month total
energy
Total energy consumption during the previous month, that is,
between midnight of the first day or the previous month and
midnight of the first day of the present month.
0.00 kWh
-1000000.00 …
1000000.00 kWh
0.01 = 1 kWh
45.36 Lifetime peak
power value
Value of the peak power over the drive lifetime. 0.00 kW
-3000.00 …
3000.00 kW
Peak power value. 10 = 1 kW
45.37 Lifetime peak
power date
Date of the peak power over the drive lifetime. 1.1.1980
Date. N/A
45.38 Lifetime peak
power time
Time of the peak power over the drive lifetime. 00:00:00
Time, N/A
46
46 Monitoring/scaling
settings
Speed supervision settings; actual signal filtering; general
scaling settings.
46.01 Speed scaling Defines the maximum speed value used to define the
acceleration ramp rate and the initial speed value used to
define the deceleration ramp rate (see parameter group 23
Speed reference ramp). The speed acceleration and
deceleration ramp times are therefore related to this value
(not to parameter 30.12 Maximum speed).
Also defines the 16-bit scaling of speed-related parameters.
The value of this parameter corresponds to 20000 in eg.
fieldbus communication.
1500.00 rpm;
1800.00 rpm
(95.20 b0)
0.10…30000.00
rpm
Acceleration/deceleration terminal/initial speed. 1 = 1 rpm
46.02 Frequency scaling Defines the maximum frequency value used to define the
acceleration ramp rate and the initial frequency value used to
define deceleration ramp rate (see parameter group 28
Frequency reference chain). The frequency acceleration and
deceleration ramp times are therefore related to this value
(not to parameter 30.14 Maximum frequency).
Also defines the 16-bit scaling of frequency-related
parameters. The value of this parameter corresponds to
20000 in eg. fieldbus communication.
50.00 Hz;
60.00 Hz
(95.20 b0)
0.10…1000.00 Hz Acceleration/deceleration terminal/initial frequency. 10 = 1 Hz
46.03 Torque scaling Defines the 16-bit scaling of torque parameters. The value of
this parameter (in percent of nominal motor torque)
corresponds to 10000 in eg. fieldbus communication.
100.0%
0.1…1000.0% Torque corresponding to 10000 on fieldbus. 10 = 1%
46.04 Power scaling Defines the output power value that corresponds to 10000 in
eg. fieldbus communication. The unit is selected by
parameter 96.16 Unit selection.
1000.00 kW
or hp
0.10 …30000.00
kW or
0.10 …40200.00 hp
Power corresponding to 10000 on fieldbus. 1 = 1 unit
No. Name/Value Description Def/FbEq16