Parameters 281
95.15 Special HW
settings
Contains hardware-related settings that can be enabled and
disabled by toggling the specific bits.
Note: The installation of the hardware specified by this
parameter may require derating of drive output, or impose
other limitations. Refer to the hardware manual of the drive.
00000000h…
FFFFFFFFh
Hardware options configuration word. 1 = 1
95.20 HW options word 1 Specifies hardware-related options that require differentiated
parameter defaults.
This parameter is not affected by a parameter restore.
0000h…FFFFh Hardware options configuration word. 1 = 1
96
96 System
Language selection; access levels; macro selection;
parameter save and restore; control unit reboot; user
parameter sets; unit selection.
96.01 Language Selects the language of the parameter interface and other
displayed information when viewed on the control panel.
Notes:
Not all languages listed below are necessarily supported.
This parameter does not affect the languages visible in the
Drive composer PC tool. (Those are specified under View -
Settings - Drive default language.)
Not selected
Not selected None. 0
English English. 1033
Deutsch German. 1031
Italiano Italian. 1040
Español Spanish. 3082
Français French. 1036
Suomi Finnish. 1035
No. Name/Value Description Def/FbEq16
Bit Name Information
0EX motor
1 ABB Sine filter 1 = An ABB sine filter is connected to the output of the drive.
2…15 Reserved
Bit Name Value
0 Supply frequency
60 Hz
See section Differences in the default values between 50 Hz and
60 Hz supply frequency settings on page 298.
0 = 50 Hz.
1 = 60 Hz.
1…12 Reserved
12 du/dt filter
activation
When active, an external du/dt filter is connected to the drive/inverter
output. The setting will limit the output switching frequency, and
force the fan of the drive/inverter module to full speed.
0 = du/dt filter inactive.
1 = du/dt filter active.
14…15 Reserved