282 Parameters
Svenska Swedish. 1053
Russki Russian. 1049
Cesky Czech. 1029
96.02 Pass code Pass codes can be entered into this parameter to activate
further access levels (see parameter 96.03 Access level
status) or to configure the user lock.
Entering “358” toggles the parameter lock, which prevents the
changing of all other parameters through the control panel or
the Drive composer PC tool.
Entering the user pass code (by default, “10000000”) enables
parameters 96.10096.102, which can be used to define a
new user pass code and to select the actions that are to be
prevented.
Entering an invalid pass code will close the user lock if open,
ie. hide parameters 96.10096.102. After entering the code,
check that the parameters are in fact hidden. If they are not,
enter another (random) pass code.
Note: You must change the default user pass code to
maintain a high level of cybersecurity. Store the code in a safe
place – the protection cannot be disabled even by ABB if the
code is lost.
See also section User lock (page 97).
0…99999999 Pass code. -
96.03 Access level status Shows which access levels have been activated by pass
codes entered into parameter 96.02 Pass code.
0001b
00000000h…
FFFFFFFFh
Active access levels. -
96.06 Parameter restore Restores the original settings of the control program, ie.
parameter default values.
Note: This parameter cannot be changed while the drive is
running.
Done
Done Restoring is completed. 0
No. Name/Value Description Def/FbEq16
Bit Name
0 End user
1 Service
2 Advanced programmer
3…10 Reserved
11 OEM access level 1
12 OEM access level 2
13 OEM access level 3
14 Parameter lock
15 Reserved