Parameters 199
On 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Other [bit] Source selection (see Terms and abbreviations on page 100). -
34.112 Boost time duration Defines the time inside which the extra time is deactivated
after extra time activation signal is switched off.
Example: If parameter 34.111 Boost time activation source is
set to DI1 and 34.112 Boost time duration is set to 00 01:30,
the extra time is active for 1 hour and 30 minutes after digital
input DI is deactivated.
00 00:00
00 00:00…07 00:00 Extra time duration. 1 = 1
35
35 Motor thermal
protection
Motor thermal protection settings such as temperature
measurement configuration, load curve definition and motor
fan control configuration.
See also section Motor thermal protection (page 84).
35.01 Motor estimated
temperature
Displays the motor temperature as estimated by the internal
motor thermal protection model (see parameters
35.50…35.55). The unit is selected by parameter 96.16 Unit
selection.
This parameter is read-only.
-
-60…1000 °C or
-76…1832 °F
Estimated motor temperature. 1 = 1°
35.02 Measured
temperature 1
Displays the temperature received through the source
defined by parameter 35.11 Temperature 1 source. The unit is
selected by parameter 96.16 Unit selection.
Note: With a PTC sensor, the value shown is not a valid
measurement. Either 0 ohm (normal temperature) or the
value of parameter 35.22 Temperature 2 fault limit (excessive
temperature) is shown.
This parameter is read-only.
-
-60…5000 °C or
-76…9032 °F,
0 ohm or
[35.12] ohm
Measured temperature 1. 1 = 1 unit
35.03 Measured
temperature 2
Displays the temperature received through the source
defined by parameter 35.21 Temperature 2 source. The unit
is selected by parameter 96.16 Unit selection.
Note: With a PTC sensor, the value shown is not a valid
measurement. Either 0 ohm (normal temperature) or the
value of parameter 35.22 Temperature 2 fault limit (excessive
temperature) is shown.
This parameter is read-only.
-
-60…5000 °C or
-76…9032 °F,
0 ohm or
[35.22] ohm
Measured temperature 2. 1 = 1 unit
No. Name/Value Description Def/FbEq16