Additional parameter data 317
34.111 Boost time activation source Binary
src
--1 = 1
34.112 Boost time duration Duration 00 00:00…07 00:00 min 1 = 1 min
35 Motor thermal protection
35.01 Motor estimated temperature Real -60…1000 °C or
-76…1832 °F
°C or °F 1 = 1 °
35.02 Measured temperature 1 Real -60…5000 °C or
-76…9032 °F,
0 ohm or
[35.12] ohm
°C, °F or
ohm
1 = 1 unit
35.03 Measured temperature 2 Real -60…5000 °C or
-76…9032 °F,
0 ohm or
[35.12] ohm
°C, °F or
ohm
1 = 1 unit
35.11 Temperature 1 source List 0…2, 5…8, 11…16, 19, 21,
22
-1 = 1
35.12 Temperature 1 fault limit Real -60…5000 °C or
-76…9032 °F
°C, °F or
ohm
1 = 1 unit
35.13 Temperature 1 warning limit Real -60…5000 °C or
-76…9032 °F
°C, °F or
ohm
1 = 1 unit
35.14 Temperature 1 AI source Analog
src
--1 = 1
35.21 Temperature 2 source List 0…2, 5…8, 11…16, 19 - 1 = 1
35.22 Temperature 2 fault limit Real -60…5000 °C or
-76…9032 °F
°C, °F or
ohm
1 = 1 unit
35.23 Temperature 2 warning limit Real -60…5000 °C or
-76…9032 °F
°C, °F or
ohm
1 = 1 unit
35.24 Temperature 2 AI source Analog
src
--1 = 1
35.31 Safe motor temperature
enable
List --1 = 1
35.50 Motor ambient temperature Real -60…100 °C or
-76…212°F
°C 1 = 1 °
35.51 Motor load curve Real 50…150 % 1 = 1%
35.52 Zero speed load Real 50…150 % 1 = 1%
35.53 Break point Real 1.00 … 500.00 Hz 100 = 1 Hz
35.54 Motor nominal temperature
rise
Real 0…300 °C or 32…572 °F °C or °F 1 = 1 °
35.55 Motor thermal time constant Real 100…10000 s 1 = 1 s
36 Load analyzer
36.01 PVL signal source Analog
src
--1 = 1
36.02 PVL filter time Real 0.00…120.00 s 100 = 1 s
36.06 AL2 signal source Analog
src
--1 = 1
36.07 AL2 signal scaling Real 0.00…32767.00 - 100 = 1
36.09 Reset loggers List 0…3 - 1 = 1
36.10 PVL peak value Real -32768.00…32767.00 - 100 = 1
No. Name Type Range Unit FbEq32