Parameters   141
19
19 Operation mode
Selection of local and external control location sources and 
operating modes.
See also section Operating modes of the drive (page 40).
19.01 Actual operation 
mode
Displays the operating mode currently used.
See parameter 19.11.
This parameter is read-only.
-
Zero None. 1
Speed Speed control (in vector motor control mode). 2
Reserved 3…9
Scalar (Hz) Frequency control in scalar motor control mode (in scalar 
motor control mode).
10
Forced magn. Motor is in magnetizing mode. 20
19.11 Ext1/Ext2 selection Selects the source for external control location EXT1/EXT2 
selection.
0 = EXT1
1 = EXT2
EXT1
EXT1 EXT1 (permanently selected). 0
EXT2 EXT2 (permanently selected). 1
FBA A MCW bit 11 Control word bit 11 received through fieldbus interface A. 2
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 3
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 4
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 5
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 6
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 7
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 8
Reserved 9…18
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 191). 19
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 191). 20
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 191). 21
Reserved 22…24
Supervision 1 Bit 0 of 32.01 Supervision status (see page 184). 25
Supervision 2 Bit 1 of 32.01 Supervision status (see page 184). 26
Supervision 3 Bit 2 of 32.01 Supervision status (see page 184). 27
Reserved 28…31
EFB MCW bit 11 Control word bit 11 received through the embedded fieldbus
interface.
32
FBA A connection 
loss
Detected communication loss of fieldbus interface A changes 
control mode to EXT2.
33
EFB connection 
loss
Detected communication loss of embedded fieldbus interface 
changes control mode to EXT2.
34
Other [bit] Source selection (see Terms and abbreviations on page 100). -