238   Parameters
46.22 At frequency 
hysteresis
Defines the “at setpoint” limits for frequency control of the 
drive. When the absolute difference between reference 
(28.96 Frequency ref ramp input) and actual frequency (01.06 
Output frequency) is smaller than 46.22 At frequency 
hysteresis, the drive is considered to be “at setpoint”. This is 
indicated by bit 8 of 06.11 Main status word.
2.00 Hz
0.00…1000.00 Hz Limit for “at setpoint” indication in frequency control. See par. 
46.02
46.31 Above speed limit Defines the trigger level for “above limit” indication in speed 
control. When actual speed exceeds the limit, bit 10 of 06.17 
Drive status word 2 is set.
1500.00 rpm; 
1800.00 rpm 
(95.20 b0)
0.00…30000.00 
rpm
“Above limit” indication trigger level for speed control. See par. 
46.01
46.32 Above frequency 
limit
Defines the trigger level for “above limit” indication in 
frequency control. When actual frequency exceeds the limit, 
bit 10 of 06.17 Drive status word 2 is set.
50.00 Hz; 
60.00 Hz 
(95.20 b0)
0.00…1000.00 Hz “Above limit” indication trigger level for frequency control. See par. 
46.02
46.41 kWh pulse scaling Defines the trigger level for the “kWh pulse” on for 50 ms. The 
output of the pulse is bit 9 of 05.22 Diagnostic word 3.
1.000 kWh
0.001… 
1000.000 kWh
 “kWh pulse” on trigger level. 1 = 1 kWh
47
47 Data storage
Data storage parameters that can be written to and read from 
using other parameters’ source and target settings.
Note that there are different storage parameters for different 
data types.
See also section Data storage parameters (page 96).
47.01 Data storage 1 
real32
Data storage parameter 1. 0.000
-2147483.000… 
2147483.000
32-bit data. -
47.02 Data storage 2 
real32
Data storage parameter 2. 0.000
-2147483.000… 
2147483.000
32-bit data. -
47.03 Data storage 3 
real32
Data storage parameter 3. 0.000
-2147483.000… 
2147483.000
32-bit data. -
No. Name/Value Description Def/FbEq16
01.06 (Hz)
0 Hz
28.96 + 46.22 (Hz)
28.96 (Hz)
28.96 - 46.22 (Hz)
Drive at setpoint
(06.11 bit 8 = 1)