96 Program features
Settings
Menu - Backups
Parameter 96.07 Parameter save manually (page 282).
User parameter sets
The drive supports four user parameter sets that can be saved to the permanent
memory and recalled using drive parameters. It is also possible to use digital inputs to
switch between user parameter sets. To change a user parameter set, the drive has
to be stopped.
A user parameter set contains all editable values in parameter groups 10…99 except
forced I/O values such as parameters 10.03 DI force selection and 10.04 DI
forced data
I/O extension module settings (group 15)
data storage parameters (group 47)
fieldbus communication settings (groups 50…53 and 58)
parameter 95.01 Supply voltage.
As the motor settings are included in the user parameter sets, make sure the settings
correspond to the motor used in the application before recalling a user set. In an
application where different motors are used with the drive, the motor ID run needs to
be performed with each motor and the results saved to different user sets. The
appropriate set can then be recalled when the motor is switched.
Settings
Menu - Primary settings - Advanced functions - User sets
Parameters 96.1096.13 (page 284).
Data storage parameters
Twelve (eight 32-bit, four 16-bit) parameters are reserved for data storage. These
parameters are unconnected by default and can be used for linking, testing and
commissioning purposes. They can be written to and read from using other
parameters’ source or target selections.
Settings
Parameter group 47 Data storage (page 238).