EasyManua.ls Logo

ABB ACQ580 - Page 289

ABB ACQ580
422 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters 285
96.12 User set I/O mode
in1
When parameter 96.11 User set save/load is set to User set
I/O mode, selects the user parameter set together with
parameter 96.13 User set I/O mode in2 as follows:
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Reserved 8…17
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 191). 18
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 191). 19
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 191). 20
Reserved 21…23
Supervision 1 Bit 0 of 32.01 Supervision status (see page 184). 24
Supervision 2 Bit 1 of 32.01 Supervision status (see page 184). 25
Supervision 3 Bit 2 of 32.01 Supervision status (see page 184). 26
Other [bit] Source selection (see Terms and abbreviations on page 100). -
96.13 User set I/O mode
in2
See parameter 96.12 User set I/O mode in1. Not selected
No. Name/Value Description Def/FbEq16
Status of source
defined by par.
96.12
Status of source
defined by par.
96.13
User parameter
set selected
00Set 1
10Set 2
01Set 3
11Set 4

Table of Contents

Other manuals for ABB ACQ580

Related product manuals