244 Parameters
50.14 FBA A reference 1 Displays raw (unmodified) reference REF1 sent by the master
(PLC) to fieldbus adapter A if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648…
2147483647
Raw REF1 sent by master to fieldbus adapter A. -
50.15 FBA A reference 2 Displays raw (unmodified) reference REF2 sent by the master
(PLC) to fieldbus adapter A if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648…
2147483647
Raw REF2 sent by master to fieldbus adapter A. -
50.16 FBA A status word Displays the raw (unmodified) status word sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
00000000h…
FFFFFFFFh
Status word sent by fieldbus adapter A to master. -
50.17 FBA A actual value
1
Displays raw (unmodified) actual value ACT1 sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648…
2147483647
Raw ACT1 sent by fieldbus adapter A to master. -
50.18 FBA A actual value
2
Displays raw (unmodified) actual value ACT2 sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648…
2147483647
Raw ACT2 sent by fieldbus adapter A to master. -
51
51 FBA A settings
Fieldbus adapter A configuration.
51.01 FBA A type Displays the type of the connected fieldbus adapter module.
0 = None. Module is not found or is not properly connected, or
is disabled by parameter 50.01 FBA A enable
1 = PROFIBUS-DP
32 = CANopen
37 = DeviceNet
128 =Ethernet
132 = PROFInet IO
135 =EtherCAT
136 =ETH Pwrlink
485 = RS-485 comm
101 = ControlNet
2222 = Ethernet/IP
502 = Modbus/TCP
This parameter is read-only.
-
No. Name/Value Description Def/FbEq16