Parameters 243
50.08 FBA A actual 2 type Selects the type and scaling of actual value 2 transmitted to
the fieldbus network through fieldbus adapter A. The scaling
of the value is defined by parameters 46.01…46.04,
depending on which actual value type is selected by this
parameter.
Speed or
frequency
Speed or frequency Type and scaling is chosen automatically according to the
currently active operation mode as follows:
Please select Speed (selection 4) or Frequency (selection 5)
manually.
0
Transparent No scaling is applied. 1
General Generic reference without a specific unit. 2
Reserved 3
Speed The scaling is defined by parameter 46.01 Speed scaling.4
Frequency The scaling is defined by parameter 46.02 Frequency scaling.5
50.09 FBA A SW
transparent source
Selects the source of the fieldbus status word when
parameter 50.06 FBA A SW sel is set to Transparent mode.
Not selected
Not selected No source selected. -
Other Source selection (see Terms and abbreviations on page 100). -
50.10 FBA A act1
transparent source
When parameter 50.07 FBA A actual 1 type is set to
Transparent, this parameter selects the source of actual value
1 transmitted to the fieldbus network through fieldbus adapter
A.
Not selected
Not selected No source selected. -
Other Source selection (see Terms and abbreviations on page 100). -
50.11 FBA A act2
transparent source
When parameter 50.08 FBA A actual 2 type is set to
Transparent, this parameter selects the source of actual value
2 transmitted to the fieldbus network through fieldbus adapter
A.
Not selected
Not selected No source selected. -
Other Source selection (see Terms and abbreviations on page 100). -
50.12 FBA A debug mode This parameter enables debug mode. Displays raw
(unmodified) data received from and sent to fieldbus adapter
A in parameters 50.13…50.18.
Disable
Disable Debug mode disabled. 0
Fast Debug mode enabled. Cyclical data update is as fast as
possible which increases CPU load on the drive.
1
50.13 FBA A control word Displays the raw (unmodified) control word sent by the
master (PLC) to fieldbus adapter A if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
00000000h…
FFFFFFFFh
Control word sent by master to fieldbus adapter A. -
No. Name/Value Description Def/FbEq16
Operation mode
(see par. 19.01)
Actual value 2 type
Speed control Speed
Frequency control Frequency