Parameters 241
Last speed Drive generates a warning (A7C1 FBA A communication) and
freezes the speed to the level the drive was operating at. This
only occurs if control is expected from the fieldbus.
The speed is determined on the basis of actual speed using
850 ms low-pass filtering.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
2
Speed ref safe Drive generates a warning (A7C1 FBA A communication) and
sets the speed to the value defined by parameter 22.41
Speed ref safe (when speed reference is being used) or
28.41 Frequency ref safe (when frequency reference is being
used). This only occurs if control is expected from the
fieldbus.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
3
Fault always Drive trips on 7510 FBA A communication. This occurs even
though no control is expected from the fieldbus.
4
Warning Drive generates an A7C1 FBA A communication warning.
This only occurs if control is expected from the fieldbus.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
5
50.03 FBA A comm loss t
out
Defines the time delay before the action defined by parameter
50.02 FBA A comm loss func is taken. Time count starts when
the communication link fails to update the message.
0.3 s
0.3…6553.5 s Time delay. 1 = 1 s
50.04 FBA A ref1 type Selects the type and scaling of reference 1 received from
fieldbus adapter A. The scaling of the reference is defined by
parameters 46.0146.04, depending on which reference
type is selected by this parameter.
Speed or
frequency
Speed or frequency Type and scaling is chosen automatically according to the
currently active operation mode as follows:
0
Transparent No scaling is applied. 1
General Generic reference without a specific unit. 2
Reserved 3
Speed The scaling is defined by parameter 46.01 Speed scaling.4
Frequency The scaling is defined by parameter 46.02 Frequency scaling.5
No. Name/Value Description Def/FbEq16
Operation mode
(see par. 19.01)
Reference 1 type
Speed control Speed
Frequency control Frequency