242 Parameters
50.05 FBA A ref2 type Selects the type and scaling of reference 2 received from
fieldbus adapter A. The scaling of the reference is defined by
parameters 46.0146.04, depending on which reference
type is selected by this parameter.
Speed or
frequency
Speed or frequency Type and scaling is chosen automatically according to the
currently active operation mode as follows:
Please select Speed (selection 4) or Frequency (selection 5)
manually.
0
Transparent No scaling is applied. 1
General Generic reference without a specific unit. 2
Reserved 3
Speed The scaling is defined by parameter 46.01 Speed scaling.4
Frequency The scaling is defined by parameter 46.02 Frequency scaling.5
50.06 FBA A SW sel Selects the source of the Status word to be sent to the
fieldbus network through fieldbus adapter A.
Auto
Auto Source of the Status word is chosen automatically. 0
Transparent mode The source selected by parameter 50.09 FBA A SW
transparent source is transmitted as the Status word to the
fieldbus network through fieldbus adapter A.
1
50.07 FBA A actual 1 type Selects the type and scaling of actual value 1 transmitted to
the fieldbus network through fieldbus adapter A. The scaling
of the value is defined by parameters 46.0146.04,
depending on which actual value type is selected by this
parameter.
Speed or
frequency
Speed or frequency Type and scaling is chosen automatically according to the
currently active operation mode as follows:
0
Transparent No scaling is applied. 1
General Generic reference without a specific unit. 2
Reserved 3
Speed The scaling is defined by parameter 46.01 Speed scaling.4
Frequency The scaling is defined by parameter 46.02 Frequency scaling.5
No. Name/Value Description Def/FbEq16
Operation mode
(see par. 19.01)
Reference 2 type
Speed control Speed
Frequency control Frequency
Operation mode
(see par. 19.01)
Actual value 1 type
Speed control Speed
Frequency control Frequency