Parameters 191
Hysteresis Action is taken whenever the signal rises above the value
defined by the limit + 0.5 · hysteresis range (32.61
Supervision 6 hysteresis). The action is deactivated when the
signal falls below the value defined by the limit - 0.5 ·
hysteresis range.
7
32.56 Supervision 6
action
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 6
exceeds its limits.
Note: This parameter does not affect the status indicated by
32.01 Supervision status.
No action
No action No warning or fault generated. 0
Warning Warning A8B5 ABB Signal supervision 6 is generated. 1
Fault Drive trips on fault 80B5 Signal supervision 6.2
Fault if running Drive trips on fault 80B0 Signal supervision 1 if the motor is
running.
3
32.57 Supervision 6
signal
Selects the signal to be monitored by signal supervision
function 6.
For the available selections, see parameter 32.07
Supervision 1 signal.
Zero
32.58 Supervision 6 filter
time
Defines a filter time constant for the signal monitored by
signal supervision 6.
0.000 s
0.000 … 30.000 s Signal filter time. 1000 = 1 s
32.59 Supervision 6 low Defines the lower limit for signal supervision 6. 0.00
-21474836.00…
21474836.00
Low limit. -
32.60 Supervision 6 high Defines the upper limit for signal supervision 6. 0.00
-21474836.00…
21474836.00
Upper limit. -
32.61 Supervision 6
hysteresis
Defines the hysteresis for the signal monitored by signal
supervision 6.
0.00
0.00…100000.00 Hysteresis. -
34
34 Timed functions
Configuration of the timed functions.
See also section Timed functions (page 70).
34.01 Timed functions
status
Status of the combined timers. The status of a combined
timer is the logical OR of all timers connected to it.
This parameter is read-only.
-
0000h…0FFFFh Status of combined timers 1…3. 1 = 1
No. Name/Value Description Def/FbEq16
Bit Name Description
0 Timed function 1 1 = Active.
1 Timed function 2 1 = Active.
2 Timed function 3 1 = Active.
3…15 Reserved