Parameters 185
32.05 Supervision 1
function
Selects the mode of signal supervision function 1. Determines
how the monitored signal (see parameter 32.07) is compared
to its lower and upper limits (32.09 and 32.10 respectively).
The action to be taken when the condition is fulfilled is
selected by 32.06.
Disabled
Disabled Signal supervision 1 not in use. 0
Low Action is taken whenever the signal falls below its lower limit. 1
High Action is taken whenever the signal rises above its upper
limit.
2
Abs low Action is taken whenever the absolute value of the signal falls
below its (absolute) lower limit.
3
Abs high Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
4
Both Action is taken whenever the signal falls below its low limit or
rises above its high limit.
5
Abs both Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
6
Hysteresis Action is taken whenever the signal rises above the value
defined by the limit + 0.5 · hysteresis range (32.11
Supervision 1 hysteresis). The action is deactivated when the
signal falls below the value defined by the limit - 0.5 ·
hysteresis range.
7
32.06 Supervision 1
action
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 1
exceeds its limits.
Note: This parameter does not affect the status indicated by
32.01 Supervision status.
No action
No action No warning or fault generated. 0
Warning Warning A8B0 ABB Signal supervision 1 is generated. 1
Fault Drive trips on fault 80B0 Signal supervision 1.2
Fault if running If running, the drive trips on fault 80B0 Signal supervision 1.3
32.07 Supervision 1
signal
Selects the signal to be monitored by signal supervision
function 1.
Frequency
Zero None. 0
Speed 01.01 Motor speed used (page 103). 1
Reserved 2
Frequency 01.06 Output frequency (page 103). 3
Current 01.07 Motor current (page
103). 4
Reserved 5
Torque 01.10 Motor torque (page 103). 6
DC voltage 01.11 DC voltage (page 103). 7
Output power 01.14 Output power (page 104). 8
AI1 12.11 AI1 actual value (page 125). 9
AI2 12.21 AI2 actual value (page 126). 10
Reserved 11…17
Speed ref ramp in 23.01 Speed ref ramp input (page 162). 18
No. Name/Value Description Def/FbEq16