104 Parameters
01.14 Output power Drive output power. The unit is selected by parameter 96.16
Unit selection. A filter time constant for this signal can be
defined by parameter 46.14 Filter time power.
-
-32768.00…
32767.00 kW or hp
Output power. 1 = 1 unit
01.15 Output power % of
motor nom
Output power in percent of the nominal motor power. -
-300.00… 300.00% Output power. 1 = 1%
01.16 Output power % of
drive nom
Output power in percent of the nominal drive power. -
-300.00… 300.00% Output power. 1 = 1%
01.17 Motor shaft power Estimated mechanical power at motor shaft. -
-32768.00…
32767.00 kW or hp
Motor shaft power. 1 = 1 unit
01.18 Inverter GWh
counter
Amount of energy that has passed through the drive (in either
direction) in full gigawatt-hours. The minimum value is zero.
-
0…65535 GWh Energy in GWh. 1 = 1 GWh
01.19 Inverter MWh
counter
Amount of energy that has passed through the drive (in either
direction) in full megawatt-hours. Whenever the counter rolls
over, 01.18 Inverter GWh counter is incremented. The
minimum value is zero.
-
0…1000 MWh Energy in MWh. 1 = 1 MWh
01.20 Inverter kWh
counter
Amount of energy that has passed through the drive (in either
direction) in full kilowatt-hours. Whenever the counter rolls
over, 01.19 Inverter MWh counter is incremented. The
minimum value is zero.
-
0…1000 kWh Energy in kWh. 10 = 1 kWh
01.24 Flux actual % Used flux reference in percent of nominal flux of motor. -
0…200% Flux reference. 1 = 1%
01.30 Nominal torque
scale
Torque that corresponds to 100% of nominal motor torque.
The unit is selected by parameter 96.16 Unit selection.
Note: This value is copied from parameter 99.12 Motor
nominal torque if entered. Otherwise the value is calculated
from other motor data.
-
0.000…4000000
N·m or lb·ft
Nominal torque. 1 = 100 unit
01.31 Ambient
temperature
Ambient temperature of the drive. Only for drive frames R6 or
larger.
-
40.0…120.0 °C or °F
Temperature. 1 = 1 °
01.50 Current hour kWh Current hour energy consumption. This is the energy of the
last 60 minutes (not necessarily continuous) the drive has
been running, not the energy of a calendar hour.
If the power is cycled, after the drive is again up and running,
the parameter value is set to the value it had before the power
cycle.
-
0.00… 1000000.00
kWh
Energy. 1 = 1 kWh
No. Name/Value Description Def/FbEq16