128 Parameters
13
13 Standard AO
Configuration of standard analog outputs.
13.02 AO force selection The source signals of the analog outputs can be overridden
for eg. testing purposes. A forced value parameter is provided
for each analog output, and its value is applied whenever the
corresponding bit in this parameter is 1.
Note: Boot and power cycle reset the force selections
(parameters 13.02 and 13.11).
0000h
0000h…FFFFh Forced values selector for analog outputs AO1 and AO2. 1 = 1
13.11 AO1 actual value Displays the value of AO1 in mA or V.
This parameter is read-only.
-
0.000…22.000 mA /
0.000…11.000 V
Value of AO1. 1 = 1 mA
13.12 AO1 source Selects a signal to be connected to analog output AO1. Output
frequency
Zero None. 0
Motor speed used 01.01 Motor speed used (page 103). 1
Reserved 2
Output frequency 01.06 Output frequency (page 103). 3
Motor current 01.07 Motor current (page 103). 4
Motor current % of
motor nominal
01.08 Motor current % of motor nom (page 103). 5
Motor torque 01.10 Motor torque (page 103). 6
DC voltage 01.11 DC voltage (page 103). 7
Output power 01.14 Output power (page 104). 8
Reserved 9
Speed ref ramp in 23.01 Speed ref ramp input (page 162). 10
Speed ref ramp out 23.02 Speed ref ramp output (page 162). 11
Speed ref used 24.01 Used speed reference (page 163). 12
Reserved
13
Freq ref used 28.02 Frequency ref ramp output (page 167). 14
Reserved 15
Process PID out 40.01 Process PID output actual (page 213). 16
Reserved 17…19
Temp sensor 1
excitation
The output is used to feed an excitation current to the
temperature sensor 1, see parameter 35.11 Temperature 1
source. See also section Motor thermal protection (page 84).
20
Temp sensor 2
excitation
The output is used to feed an excitation current to the
temperature sensor 2, see parameter 35.21 Temperature 2
source. See also section Motor thermal protection (page 84).
21
No. Name/Value Description Def/FbEq16
Bit Value
0 1 = Force AO1 to value of parameter 13.13 AO1 forced value. (0 = Normal mode)
1 1 = Force AO2 to value of parameter 13.23 AO2 forced value. (0 = Normal mode)
2…15 Reserved