Parameters 129
Reserved 21…25
Abs motor speed
used
01.61 Abs motor speed used (page 106). 26
Abs motor speed % 01.62 Abs motor speed % (page 106). 27
Abs output
frequency
01.63 Abs output frequency (page 106). 28
Reserved 29
Abs motor torque 01.64 Abs motor torque (page 106). 30
Abs output power 01.65 Abs output power (page 106). 31
Abs motor shaft
power
01.68 Abs motor shaft power (page 106). 32
External PID1 out 71.01 External PID act value ((page 254). 33
Reserved 34…36
AO1 data storage 13.91 AO1 data storage (page 133). 37
AO2 data storage 13.92 AO2 data storage (page 133). 38
Other Source selection (see Terms and abbreviations on page 100). -
13.13 AO1 forced value Forced value that can be used instead of the selected output
signal. See parameter 13.02 AO force selection.
0.000 mA
0.000…22.000 mA /
0.000…11.000 V
Forced value for AO1. 1 = 1 unit
13.15 AO1 unit selection Selects the unit for readings and settings related to analog
input AO1.
mA
V Volts. 2
mA Milliamperes. 10
13.16 AO1 filter time Defines the filtering time constant for analog output AO1. 0.100 s
0.000 … 30.000 s Filter time constant. 1000 = 1 s
No. Name/Value Description Def/FbEq16
63
%
100
T
t
O = I × (1 - e
-t/T
)
I = filter input (step)
O = filter output
t = time
T = filter time constant
Unfiltered signal
Filtered signal