334 Additional parameter data
96.08 Control board boot List 0…1 - 1 = 1
96.10 User set status List 0…7, 20…23 - 1 = 1
96.11 User set save/load List 0…5, 18…21 - 1 = 1
96.12 User set I/O mode in1 Binary
src
---
96.13 User set I/O mode in2 Binary
src
---
96.16 Unit selection PB 000h…FFFFh 1 = 1
96.20 Time sync primary source List 0, 2, 6, 8, 9 - 1 = 1
96.51 Clear fault and event logger Real 0…1 - 1 = 1
96.70 Disable adaptive program List 0…1 - 1 = 1
96.100 Change user pass code Data 10000000…99999999 - 1 = 1
96.101 Confirm user pass code Data 10000000…99999999 - 1 = 1
96.102 User lock functionality PB 0000h…FFFFh - 1 = 1
97 Motor control
97.01 Switching frequency reference List 4, 8, 12 kHz 1 = 1 kHz
97.02 Minimum switching frequency List 2, 4, 8, 12 kHz 1 = 1 kHz
97.03 Slip gain Real 0…200 % 1 = 1%
97.04 Voltage reserve Real -4…50 % 1 = 1%
97.05 Flux braking List 0…2 - 1 = 1
97.08 Optimizer minimum torque Real 0.0 … 1600.0 % 10 = 1%
97.09 Switching frequency mode List 0…1 - 1 = 1
97.10 Signal injection List 0…4 - 1 = 1
97.11 TR tuning Real 25…400 % 1 = 1%
97.13 IR compensation Real 0.00…50.00 % 100 = 1%
97.15 Motor model temperature
adaptation
List 0…1 - 1 = 1
97.20 U/F ratio List 0…1 - 1 = 1
98 User motor parameters
98.01 User motor model mode List 0…1 - 1 = 1
98.02 Rs user Real 0.0000…0.50000 p.u. 100000 =
1 p.u.
98.03 Rr user Real 0.0000…0.50000 p.u. 100000 =
1 p.u.
98.04 Lm user Real 0.00000…10.00000 p.u. 100000 =
1 p.u.
98.05 SigmaL user Real 0.00000…1.00000 p.u. 100000 =
1 p.u.
98.06 Ld user Real 0.00000…10.00000 p.u. 100000 =
1 p.u.
98.07 Lq user Real 0.00000…10.00000 p.u. 100000 =
1 p.u.
98.08 PM flux user Real 0.00000…2.00000 p.u. 100000 =
1 p.u.
No. Name Type Range Unit FbEq32