Parameters 283
Restore defaults Restores all editable parameter values to default values,
except
• motor data and ID run results
• I/O extension module settings
• end user texts, such as customized warnings and faults,
and the drive name
• control panel/PC communication settings
• fieldbus adapter settings
• control macro selection and the parameter defaults
implemented by it
• parameter 95.01 Supply voltage
• differentiated defaults implemented by parameters 95.20
HW options word 1
• user lock configuration parameters 96.100…96.102.
8
Clear all Restores all editable parameter values to default values,
except
• end user texts, such as customized warnings and faults,
and the drive name
• control panel/PC communication settings
• user lock configuration parameters 96.100…96.102.
• group 49 Panel port communication parameters.
62
Reset all fieldbus
settings
Restores all fieldbus and communication related settings to
default values.
Note: Fieldbus, control panel and PC tool communication are
interrupted during the restore.
32
Reset home view Restores the home view layout back to show the values of the
default parameters defined by the control macro in use
512
Reset end user
texts
Restores all end user texts to default values, including the
drive name, contact info, customized fault and warning texts,
PID unit and currency unit.
1024
Reset motor data Restores all motor nominal values and motor ID run results to
default values.
2
All to factory
defaults
• Restores all drive parameters and settings back to initial
factory values.
34560
96.07 Parameter save
manually
Saves the valid parameter values to the permanent memory
on the drive control unit to ensure that operation can continue
after cycling the power. Save the parameters with this
parameter
• to store values sent from the fieldbus
• when using external +24 V DC power supply to the control
unit: to save parameter changes before you power down
the control unit. The supply has a very short hold-up time
when powered off.
Note: A new parameter value is saved automatically when
changed from the PC tool or control panel but not when
altered through a fieldbus adapter connection.
Done
Done Save completed. 0
Save Save in progress. 1
96.08 Control board boot Changing the value of this parameter to 1 reboots the control
unit (without requiring a power off/on cycle of the complete
drive module).
The value reverts to 0 automatically.
No action
No action 1 = No action. 0
Reboot 1 = Reboot the control unit. 1
No. Name/Value Description Def/FbEq16