140 Parameters
15.34 Freq out 1 src min Defines the real value of the signal (selected by parameter
15.33 Freq out 1 source) that corresponds to the minimum
value of frequency output 1 (defined by parameter 15.36 Freq
out 1 at src min). This applies when 15.22 DO1 configuration
is set to Frequency output.
0.000
-32768.000…
32767.000
Real signal value corresponding to minimum value of
frequency output 1.
1 = 1
15.35 Freq out 1 src max Defines the real value of the signal (selected by parameter
15.33 Freq out 1 source) that corresponds to the maximum
value of frequency output 1 (defined by parameter 15.37 Freq
out 1 at src max). This applies when 15.22 DO1 configuration
is set to Frequency output.
See parameter 15.34 Freq out 1 src min.
1500.000;
1800.000
(95.20 b0)
-32768.000…
32767.000
Real signal value corresponding to maximum value of
frequency output 1.
1 = 1
15.36 Freq out 1 at src
min
Defines the minimum output value of frequency output 1
when 15.22 DO1 configuration is set to Frequency output.
See also drawing at parameter 15.34 Freq out 1 src min.
0 Hz
0 16000 Hz Minimum frequency output 1 value. 1 = 1 Hz
15.37 Freq out 1 at src
max
Defines the maximum value of frequency output 1 when
15.22 DO1 configuration is set to Frequency output.
See also drawing at parameter 15.34 Freq out 1 src min.
16000 Hz
0 16000 Hz Maximum value of frequency output 1. 1 = 1 Hz
No. Name/Value Description Def/FbEq16
15.37
15.36
15.35 15.34
15.3515.34
15.37
15.36
Signal (real)
selected by par.
15.33
Signal (real)
selected by par.
15.33
(Hz)
(Hz)