Parameters 137
15.08 RO4 ON delay Defines the activation delay for relay output RO4. 0.0 s
t
On
= 15.08 RO4 ON delay
t
Off
= 15.09 RO4 OFF delay
0.0 3000.0 s Activation delay for RO4. 10 = 1 s
15.09 RO4 OFF delay Defines the deactivation delay for relay output RO4. See
parameter 15.08 RO4 ON delay.
0.0 s
0.0 3000.0 s Deactivation delay for RO4. 10 = 1 s
15.10 RO5 source Selects a drive signal to be connected to relay output RO5.
For the available selections, see parameter 15.07 RO4
source.
Not
energized
15.11 RO5 ON delay Defines the activation delay for relay output RO5. 0.0 s
t
On
= 15.11 RO5 ON delay
t
Off
= 15.12 RO5 OFF delay
0.0 3000.0 s Activation delay for RO5. 10 = 1 s
15.12 RO5 OFF delay Defines the deactivation delay for relay output RO5. See
parameter 15.11 RO5 ON delay.
0.0 s
0.0 3000.0 s Deactivation delay for RO5. 10 = 1 s
15.22 DO1 configuration Selects how DO1 is used. Digital output
Digital output DO1 is used as a digital output. 0
Frequency output DO1 is used as a frequency output. 2
15.23 DO1 source Selects a drive signal to be connected to digital output DO1
when 15.22 DO1 configuration is set to Digital output.
Not
energized
Not energized Output is not energized. 0
Energized Output is energized. 1
Ready run Bit 1 of 06.11 Main status word (see page 111). 2
Reserved 3
Enabled Bit 0 of 06.16 Drive status word 1 (see page 112 ). 4
Started Bit 5 of 06.16 Drive status word 1 (see page 112 ). 5
No. Name/Value Description Def/FbEq16
1
0
1
0
t
On
t
Off
t
On
t
Off
Status of selected
source
RO status
Time
1
0
1
0
t
On
t
Off
t
On
t
Off
Status of selected
source
RO status
Time