Parameters 135
15.05 RO/DO force
selection
The electrical statuses of the relay/digital outputs can be
overridden for eg. testing purposes. A bit in parameter 15.06
RO/DO forced data is provided for each relay or digital output,
and its value is applied whenever the corresponding bit in this
parameter is 1.
Note: Boot and power cycle reset the force selections
(parameters 15.05 and 15.06).
0000h
0000h…FFFFh Override selection for relay/digital outputs. 1 = 1
15.06 RO/DO forced data Allows the data value of a forced relay or digital output to be
changed from 0 to 1. It is only possible to force an output that
has been selected in parameter 15.05 RO/DO force selection.
Bits 0…1 are the forced values for RO4…RO5; bit 5 is the
forced value for DO1.
0000h
0000h…FFFFh Forced values of relay/digital outputs. 1 = 1
15.07 RO4 source Selects a drive signal to be connected to relay output RO4. Not
energized
Not energized Output is not energized. 0
Energized Output is energized. 1
Ready run Bit 1 of 06.11 Main status word (see page 111). 2
Reserved 3
Enabled Bit 0 of 06.16 Drive status word 1 (see page 112 ). 4
Started Bit 5 of 06.16 Drive status word 1 (see page 112 ). 5
Magnetized Bit 1 of 06.17 Drive status word 2 (see page 112 ). 6
Running Bit 6 of 06.16 Drive status word 1 (see page 112). 7
Ready ref Bit 2 of 06.11 Main status word (see page 111). 8
At setpoint Bit 8 of 06.11 Main status word (see page 111). 9
Reverse Bit 2 of 06.19 Speed control status word (see page 113). 10
Zero speed Bit 0 of 06.19 Speed control status word (see page 113). 11
No. Name/Value Description Def/FbEq16
Bit Value
0 1 = Force RO4 to value of bit 0 of parameter 15.06 RO/DO forced data.
1 1 = Force RO5 to value of bit 1 of parameter 15.06 RO/DO forced data.
2…4 Reserved
5 1 = Force DO1 to value of bit 5 of parameter 15.06 RO/DO forced data.
6…15 Reserved
Bit Name Description
0 RO4 Force the value of this bit to RO4, if so defined in parameter 15.05 RO/DO
force selection.
1 RO5 Force the value of this bit to RO5, if so defined in parameter 15.05 RO/DO
force selection.
2…4 Reserved
5 DO1 1Force the value of this bit to DO1 if so defined in parameter 15.05 RO/DO
force selection.
6…15 Reserved