Additional parameter data 319
37.17 ULC frequency table point 2 Real -500.0…500.0 Hz 10 = 1 Hz
37.18 ULC frequency table point 3 Real -500.0…500.0 Hz 10 = 1 Hz
37.19 ULC frequency table point 4 Real -500.0…500.0 Hz 10 = 1 Hz
37.20 ULC frequency table point 5 Real -500.0…500.0 Hz 10 = 1 Hz
37.21 ULC underload point 1 Real -1600.0…1600.0 % 10 = 1%
37.22 ULC underload point 2 Real -1600.0…1600.0 % 10 = 1%
37.23 ULC underload point 3 Real -1600.0…1600.0 % 10 = 1%
37.24 ULC underload point 4 Real -1600.0…1600.0 % 10 = 1%
37.25 ULC underload point 5 Real -1600.0…1600.0 % 10 = 1%
37.31 ULC overload point 1 Real -1600.0…1600.0 % 10 = 1%
37.32 ULC overload point 2 Real -1600.0…1600.0 % 10 = 1%
37.33 ULC overload point 3 Real -1600.0…1600.0 % 10 = 1%
37.34 ULC overload point 4 Real -1600.0…1600.0 % 10 = 1%
37.35 ULC overload point 5 Real -1600.0…1600.0 % 10 = 1%
37.41 ULC overload timer Real 0.0…10000.0 s 10 = 1 s
37.42 ULC underload timer Real 0.0…10000.0 s 10 = 1 s
40 Process PID set 1
40.01 Process PID output actual Real -200000.00…200000.00 % 100 = 1 PID
customer unit
40.02 Process PID feedback actual Real -200000.00…200000.00 PID
customer
units
100 = 1 PID
customer unit
40.03 Process PID setpoint actual Real -200000…200000 PID
customer
units
100 = 1 PID
customer unit
40.04 Process PID deviation actual Real -200000.00…200000.00 PID
customer
units
100 = 1 PID
customer unit
40.06 Process PID status word PB 0000h…FFFFh - 1 = 1
40.07 Process PID operation mode List 0…2 - 1 = 1
40.08 Set 1 feedback 1 source Analog
src
--1 = 1
40.09 Set 1 feedback 2 source Analog
src
--1 = 1
40.10 Set 1 feedback function List 0…13 - 1 = 1
40.11 Set 1 feedback filter time Real 0.000…30.000 s 1000 = 1 s
40.14 Set 1 setpoint scaling Real -200000.00…200000.00 - 100 = 1
40.15 Set 1 output scaling Real -200000.00…200000.00 - 100 = 1
40.16 Set 1 setpoint 1 source Analog
src
--1 = 1
40.17 Set 1 setpoint 2 source Analog
src
--1 = 1
40.18 Set 1 setpoint function List 0…13 - 1 = 1
40.19 Set 1 internal setpoint sel1 Binary
src
--1 = 1
No. Name Type Range Unit FbEq32