ACS550 User’s Manual 113
Parameters
13 = DI3,4,5 – Selects one of seven Constant Speeds (1…7) using DI3, DI4 and DI5.
See above (
DI1,2,3) for code.
14 =
DI4,5,6 – Selects one of seven Constant Speeds (1…7) using DI4, DI5 and DI6.
See above (
DI1,2,3) for code.
15…18 =
TIMED FUNC 1…4 – Selects Constant Speed 1 when Timed Function is active. See Group 36: TIMED
FUNCTIONS.
19 =
TIMED FUN1&2 – Selects a constant speed depending on the state of Timed Functions 1 & 2. See parameter
1209.
-1 =
DI1(INV) – Selects Constant Speed 1 with digital input DI1.
Inverse operation: Digital input de-activated = Constant Speed 1 activated.
-2…- 6 =
DI2(INV)…DI6(INV) – Selects Constant Speed 1 with digital input. See above.
-7 =
DI1,2(INV) – Selects one of three Constant Speeds (1…3) using DI1 and DI2.
Inverse operation uses two digital inputs, as defined below (0 =
DI de-activated, 1 = DI activated):
-8 =
DI2,3(INV) – Selects one of three Constant Speeds (1…3) using DI2 and DI3.
See above (
DI1,2(INV)) for code.
-9 =
DI3,4(INV) – Selects one of three Constant Speeds (1…3) using DI3 and DI4.
See above (
DI1,2(INV)) for code.
-10 =
DI4,5(INV) – Selects one of three Constant Speeds (1…3) using DI4 and DI5.
See above (
DI1,2(INV)) for code.
-11 =
DI5,6(INV) – Selects one of three Constant Speeds (1…3) using DI5 and DI6.
See above (
DI1,2(INV)) for code.
-12 =
DI1,2,3(INV) – Selects one of seven Constant Speeds (1…7) using DI1, DI2 and DI3.
Inverse operation uses three digital inputs, as defined below (0 =
DI de-activated, 1 = DI activated):
-13 =
DI3,4,5(INV) – Selects one of seven Constant Speeds (1…7) using DI3, DI4 and DI5.
See above (
DI1,2,3(INV)) for code.
-14 =
DI4,5,6(INV) – Selects one of seven Constant Speeds (1…7) using DI4, DI5 and DI6.
See above (
DI1,2,3(INV)) for code.
1202 CONST SPEED 1
Sets value for Constant Speed 1.
The range and units depend on parameter 9904
MOTOR CTRL MODE.
Range: 0…30000 rpm when 9904 = 1 (
VECTOR:sPEED) or 2 (VECTOR:TORQ).
Range: 0…500 Hz when 9904 = 3 (
SCALAR:FREQ).
1203
1208
CONST SPEED 2…CONST SPEED 7
Each sets a value for a Constant Speed. See
CONST SPEED 1 above.
Constant Speed 7 is used also as jogging speed. See parameter 1004
JOGGING SEL.
Code Description
DI1 DI2 Function
1 1 No constant speed
0 1 Constant speed 1 (1202)
1 0 Constant speed 2 (1203)
0 0 Constant speed 3 (1204)
DI1 DI2 DI3 Function
1 1 1 No constant speed
0 1 1 Constant speed 1 (1202)
1 0 1 Constant speed 2 (1203)
0 0 1 Constant speed 3 (1204)
1 1 0 Constant speed 4 (1205)
0 1 0 Constant speed 5 (1206)
1 0 0 Constant speed 6 (1207)
0 0 0 Constant speed 7 (1208)