62 ACS550 User’s Manual
Control panels
Basic Control Panel
Features
The Basic Control Panel features:
numeric control panel with an LCD display
copy function – parameters can be copied to the control panel memory for later
transfer to other drives or for backup of a particular system.
Overview
The following table summarizes the key functions and displays on the Basic Control
Panel.
No. Use
1 LCD display – Divided into five areas:
a. Upper left – Control location:
LOC: drive control is local, that is, from the control panel
REM: drive control is remote, such as the drive I/O or fieldbus.
b. Upper right – Unit of the displayed value.
c. Center – Variable; in general, shows parameter and signal values, menus or
lists. Shows also fault and alarm codes.
d. Lower left and center – Panel operation state:
OUTPUT: Output mode
PAR: Parameter mode
MENU: Main menu
: Fault mode.
e. Lower right – Indicators:
FWD (forward) / REV (reverse): direction of the motor rotation
Flashing slowly: stopped
Flashing rapidly: running, not at setpoint
Steady: running, at setpoint
: Displayed value can be modified (in the Parameter and Reference
modes).
2 RESET/EXIT – Exits to the next higher menu level without saving changed
values. Resets faults in the Output and Fault modes.
3 MENU/ENTER – Enters deeper into menu level. In the Parameter mode,
saves the displayed value as the new setting.
4 Up –
Scrolls up through a menu or list.
Increases a value if a parameter is selected.
Increases the reference value in the Reference mode.
Holding the key down changes the value faster.
5 Down –
Scrolls down through a menu or list.
Decreases a value if a parameter is selected.
Decreases the reference value in the Reference mode.
Holding the key down changes the value faster.
6 LOC/REM – Changes between local and remote control of the drive.
7 DIR – Changes the direction of the motor rotation.
8 STOP – Stops the drive in local control.
9 START – Starts the drive in local control.
FAULT
SET
RESET
EXIT
MENU
ENTER
2
3
4
5
6 7
8 9
1c
LOC A
OUTPUT FWD
11
.
1b
1e
1a
1d