Group 29: MAINTENANCE TRIG
This group contains usage levels and trigger points. When usage reaches the set
trigger point, a notice displayed on the control panel signals that maintenance is due.
Code Description
2901 COOLING FAN TRIG
Sets the trigger point for the drive’s cooling fan counter.
Value is compared to parameter 2902 value.
0.0 – Disables the trigger.
2902 COOLING FAN ACT
Defines the actual value of the drive’s cooling fan counter.
When parameter 2901 has been set to a non-zero value, the counter starts.
When the actual value of the counter exceeds the value defined by parameter 2901, a maintenance notice is
displayed on the panel.
0.0 – Resets the parameter.
2903 REVOLUTION TRIG
Sets the trigger point for the motor’s accumulated revolutions counter.
Value is compared to parameter 2904 value.
0 – Disables the trigger.
2904 REVOLUTION ACT
Defines the actual value of the motor’s accumulated revolutions counter.
When parameter 2903 has been set to a non-zero value, the counter starts.
When the actual value of the counter exceeds the value defined by parameter 2903, a maintenance notice is
displayed on the panel.
0 – Resets the parameter.
2905 RUN TIME TRIG
Sets the trigger point for the drive’s run time counter.
Value is compared to parameter 2906 value.
0.0 – Disables the trigger.
2906 RUN TIME ACT
Defines the actual value of the drive’s run time counter.
When parameter 2905 has been set to a non-zero value, the counter starts.
When the actual value of the counter exceeds the value defined by parameter 2905, a maintenance notice is
displayed on the panel.
0.0 – Resets the parameter.
2907 USER MWh TRIG
Sets the trigger point for the drive’s accumulated power consumption (in megawatt hours) counter.
Value is compared to parameter 2908 value.
0.0 – Disables the trigger.
2908 USER MWh ACT
Defines the actual value of the drive’s accumulated power consumption (in megawatt hours) counter.
When parameter 2907 has been set to a non-zero value, the counter starts.
When the actual value of the counter exceeds the value defined by parameter 2907, a maintenance notice is
displayed on the panel.
0.0 – Resets the parameter.