EasyManua.ls Logo

ABB ACS550 - Analog Output Control; Relay Output Control

ABB ACS550
310 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACS550 User’s Manual 195
Embedded fieldbus
Relay output control
Using the fieldbus for relay output control requires:
drive parameter values set as defined below
fieldbus controller supplied, binary coded, relay command(s) in the appropriate
location. (The location is defined by the Protocol Reference, which is protocol
dependent.)
Note: Relay status feedback occurs without configuration as defined below.
Analog output control
Using the fieldbus for analog output control (e.g. PID setpoint) requires:
drive parameter values set as defined below
fieldbus controller supplied analog value(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Drive parameter Value Description
Modbus protocol reference
ABB DRV DCU PROFILE
1401 RELAY OUTPUT 1 35 (COMM) Relay Output 1 controlled
by fieldbus.
40134 bit 0 or 00033
1402
RELAY OUTPUT 2 35 (COMM) Relay Output 2 controlled
by fieldbus.
40134 bit 1 or 00034
1403
RELAY OUTPUT 3 35 (COMM) Relay Output 3 controlled
by fieldbus.
40134 bit 2 or 00035
1410
1
RELAY
OUTPUT 4 35 (COMM) Relay Output 4 controlled
by fieldbus.
40134 bit 3 or 00036
1411
1
RELAY
OUTPUT 5 35 (COMM) Relay Output 5 controlled
by fieldbus.
40134 bit 4 or 00037
1412
1
RELAY
OUTPUT 6 35 (COMM) Relay Output 6 controlled
by fieldbus.
40134 bit 5 or 00038
1
More than 3 relays requires the addition of a relay extension module.
Drive parameter Description
Modbus
protocol
reference
ABB DRV DCU PROFILE
0122 RO 1-3 STATUS Relay 1…3 status. 40122
0123
RO 4-6 STATUS Relay 4…6 status. 40123
Drive parameter Value Description
Modbus
protocol
reference
ABB DRV DCU PROFILE
1501 AO1 CONTENT SEL 135 (COMM VALUE 1) Analog Output 1
controlled by writing to
parameter 0135.
0135
COMM VALUE 1 40135
1507
AO2 CONTENT SEL 136 (COMM VALUE 2) Analog Output 2
controlled by writing to
parameter 0136.
0136
COMM VALUE 2 40136

Table of Contents

Other manuals for ABB ACS550

Related product manuals