EasyManua.ls Logo

ABB ACS550 - Connection Example of a Two-Wire Sensor

ABB ACS550
310 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
80 ACS550 User’s Manual
Application macros
Connection example of a two-wire sensor
Many applications use process PI(D) and need a feedback signal from the process.
The feedback signal is typically connected to analog input 2 (AI2). The macro wiring
diagrams in this chapter show the connection when a separately powered sensor is
used. The figure below gives an example of a connection using a two-wire sensor.
Note: The sensor is supplied through its current output. Thus the output signal must
be 4…20 mA, not 0…20 m A.
X1 / control board
5 AI2 Process actual value measurement,
0(4) 20 mA, R
in
= 100 ohm
6AGND
X1 / control board
10 +24 V Auxiliary voltage output, non-isolated,
24 V DC, 250 mA
11 GND
P
I
4…20 mA

Table of Contents