132 ACS550 User’s Manual
Parameters
2208 EMERG DEC TIME
Sets the deceleration time for maximum frequency to zero for an emergency.
See parameter 2109
EMERG STOP SEL.
Ramp is linear.
2209 RAMP INPUT 0
Defines control for forcing the ramp input to 0.
0 =
NOT SEL – Not selected.
1 =
DI1 – Defines digital input DI1 as the control for forcing the ramp input to 0.
Activating the digital input forces ramp input to 0. Ramp output will ramp to 0 according to the currently used ramp
time, after which it will stay at 0.
De-activating the digital input: ramp resumes normal operation.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the control for forcing the ramp input to 0.
See
DI1 above.
7 =
COMM – Defines bit 13 of the Command Word 1 as the control for forcing the ramp input to 0.
The Command Word is supplied through fieldbus communication.
The Command Word is parameter 0301.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as the control for forcing the ramp input to 0.
De-activating the digital input forces ramp input to 0.
Activating the digital input: ramp resumes normal operation.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the control for forcing the ramp function
generator input to 0.
See
DI1(INV) above.
Code Description