142 ACS550 User’s Manual
Parameters
3018 COMM FAULT FUNC
Defines the drive response if the fieldbus communication is lost.
0 =
NOT SEL – No response.
1 =
FAULT – Displays a fault (28, SERIAL 1 ERR) and the drive coasts to stop.
2 =
CONST SP 7 – Displays an alarm (2005, I/O COMM) and sets speed using 1208 CONST SPEED 7. This “alarm speed”
remains active until the fieldbus writes a new reference value.
3 =
LAST SPEED – Displays an alarm (2005, I/O COMM) and sets speed using the last operating level. This value is the
average speed over the last 10 seconds. This “alarm speed” remains active until the fieldbus writes a new
reference value.
WARNING! If you select
CONST SP 7, or LAST SPEED, make sure that continued operation is safe when
fieldbus communication is lost.
3019 COMM FAULT TIME
Sets the communication fault time used with 3018 COMM FAULT FUNC.
Brief interruptions in the fieldbus communication are not treated as faults if they are less than the
COMM FAULT TIME
value.
3021 AI1 FAULT LIMIT
Sets a fault level for analog input 1.
See 3001
AI<MIN FUNCTION.
3022 AI2 FAULT LIMIT
Sets a fault level for analog input 2.
See 3001
AI<MIN FUNCTION.
3023 WIRING FAULT
Defines the drive response to cross wiring faults and to ground faults detected when the drive is NOT running. When
the drive is not running it monitors for:
Improper connections of input power to the drive output (the drive can display fault 35,
OUTPUT WIRING if improper
connections are detected).
Ground faults (the drive can display fault 16,
EARTH FAULT if a ground fault is detected). Also, see parameter 3017
EARTH FAULT.
0 =
DISABLE – No drive response to either of the above monitoring results.
1 =
ENABLE – The drive displays faults when this monitoring detects problems.
3024 CB TEMP FAULT
Defines the drive response to control board overheating. Not for drives with an OMIO control board.
0 = DISABLE – No response.
1 =
ENABLE – Displays fault 37 (CB OVERTEMP) and the drive coasts to stop.