ACS550 User’s Manual 179
Parameters
The table below shows the ACS550 PFC motor assignments for some typical settings in the Relay Output
parameters (1401…1403 and 1410…1412), where the settings are either =31 (
PFC), or =X (anything but 31), and
where the Autochange function is disabled (8118
AUTOCHNG INTERV = 0).
The table below shows the ACS550 PFC motor assignments for some typical settings in the Relay Output
parameters (1401…1403 and 1410…1412), where the settings are either =31 (
PFC), or =X (anything but 31), and
where the Autochange function is enabled (8118
AUTOCHNG INTERV = value > 0).
8118 AUTOCHNG INTERV
Controls operation of the Autochange function and sets the
interval between changes.
The Autochange time interval only applies to the time when
the speed regulated motor is running.
See parameter 8119
AUTOCHNG LEVEL for an overview of the
Autochange function.
The drive always coasts to stop when autochange is
performed.
Autochange enabled requires parameter 8120
INTERLOCKS =
value > 0.
-0.1 =
TEST MODE – Forces the interval to value 36…48 s.
0.0 =
NOT SEL – Disables the Autochange function.
0.1…336 – The operating time interval (the time when the start
signal is on) between automatic motor changes.
WARNING! When enabled, the Autochange function
requires the interlocks (8120
INTERLOCKS = value > 0)
enabled. During autochange the power output is
interrupted and the drive coasts to stop, preventing
damage to the contacts.
Code Description
Parameter setting ACS550 Relay assignment
1
4
0
1
1
4
0
2
1
4
0
3
1
4
1
0
1
4
1
1
1
4
1
2
8
1
1
7
Autochange disabled
RO1 RO2 RO3 RO4 RO5 RO6
31 X X X X X 1 Aux. X X X X X
31 31 X X X X 2 Aux. Aux. X X X X
31 31 31 X X X 3 Aux. Aux. Aux. X X X
X 31 31 X X X 2 X Aux. Aux. X X X
X X X 31 X 31 2 X X X Aux. X Aux.
31 31 X X X X 1* Aux. Aux. X X X X
* = One additional relay output for the PFC that is in use. One motor is in “sleep”
when the other is rotating.
Parameter setting ACS550 Relay assignment
1
4
0
1
1
4
0
2
1
4
0
3
1
4
1
0
1
4
1
1
1
4
1
2
8
1
1
7
Autochange enabled
RO1 RO2 RO3 RO4 RO5 RO6
31 31 X X X X 1 PFC PFC X X X X
31 31 31 X X X 2 PFC PFC PFC X X X
X 31 31 X X X 1 X PFC PFC X X X
X X X 31 X 31 1 X X X PFC X PFC
31 31 X X X X 0** PFC PFC X X X X
** = No auxiliary motors, but the autochange function is in use. Working as a
standard PID-control.
PFC with Autochange mode
ACS550
Relay logic