ACS550 User’s Manual 227
Fieldbus adapter
Relay output control
Using the fieldbus for relay output control requires:
• drive parameter values set as defined below
• fieldbus controller supplied, binary coded, relay command(s) in the appropriate
location. (The location is defined by the Protocol Reference, which is protocol
dependent.)
Note: Relay status feedback occurs without configuration as defined below.
Analog output control
Using the fieldbus for analog output control (e.g. PID setpoint) requires:
• drive parameter values set as defined below
• fieldbus controller supplied analog value(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
Drive parameter Value Description
Protocol
reference
1401
RELAY OUTPUT 1 35 (COMM)
36 (
COMM(-1))
Relay Output 1 controlled by fieldbus.
1402
RELAY OUTPUT 2 Relay Output 2 controlled by fieldbus.
1403
RELAY OUTPUT 3 Relay Output 3 controlled by fieldbus.
1410
1
RELAY
OUTPUT 4 Relay Output 4 controlled by fieldbus.
1411
1
RELAY
OUTPUT 5 Relay Output 5 controlled by fieldbus.
1412
1
RELAY
OUTPUT 6 Relay Output 6 controlled by fieldbus.
1
More than 3 relays requires the addition of a relay extension module.
Drive parameter Value Protocol reference
0122 RO 1-3 STATUS Relay 1…3 status.
0123
RO 4-6 STATUS Relay 4…6 status.
Drive parameter Value Description
Protocol
reference
1501 AO1 CONTENT SEL 135 (COMM VALUE 1) Analog Output 1 controlled by
writing to parameter 0135.
–
0135
COMM VALUE 1–
1502
…
1505
AO1 CONTENT MIN
…
MAXIMUM AO1
Set appropriate
values.
Used for scaling –
1506
FILTER AO1 Filter time constant for AO1. –
1507
AO2 CONTENT SEL 136 (COMM VALUE 2) Analog Output 2 controlled by
writing to parameter 0136.
–
0136
COMM VALUE 2–
1508
…
1511
AO2 CONTENT MIN
…
MAXIMUM AO2
Set appropriate
values.
Used for scaling –
1512
FILTER AO2 Filter time constant for AO2. –