ActionTemperature
range
Frame
Derating not required0…+40 °C
R3…R8
+32…+104 °F
Derating required+40...+50 °C
+104...+122 °F
The output current is calculated by the current given in the rating tables multiplying
by the derating factor (k, as shown in the following figure)
125
Frames R0...R2
Frames R3...R8
Frames R1...R3
T
1.00
0.90
k
0.80
0.85
0.95
0.95
-15 °C
5 °
F
...
50 °C
122 °F
55 °C
131 °F
T
1.00
0.90
k
0.80
0.85
0.95
0.90
-15 °C
5 °
F
...
40 °C
104 °F
45 °C
113 °F
50 °C
122 °F
T
1.00
0.90
k
0.80
0.85
0.95
0.90
-15 °C
5 °
F
...
50 °C
122 °F
55 °C
131 °F
60 °C
140 °F
■
Altitude derating
In altitudes 1000…4000 m (3300…13120 ft) above sea level, the derating is 1% for
every 100 m (330 ft).
The output current is calculated by multiplying the current given in the rating table
by the derating factor k, which for x meters (1000 m <= x <= 4000 m) is:
142 Technical data