Operational functionality and motor cable lengthMaximum recommended
motor cable length The drive is designed to operate with optimum performance
with the following maximum motor cable lengths.
Maximum motor cable length, 4 kHzFrame size
Vector controlScalar control
ftmftm
Standard drive, without external options
330100330100R0*
330100330100R1*
330100330100R2*
990300990300R3
990300990300R4
990300990300R5
990300990300R6
990300990300R7
990300990300R8
3AXD10000561047.xls A
Note 1: In multi-motor system, the sum of all motor cable lengths
shall not exceed that given in the following table.
Note 2: Longer cables cause a motor voltage decrease which
limits the available motor power. The decrease in voltage de-
pends on the motor cable length and characteristics. A sine filter
(optional) at the drive output can also cause a decrease in
voltage. For more information, consult your local ABB Service
representative (http://new.abb.com/channel-partners/search).
*)Conducted and radiated emissions of these motor cable
lengths do not comply with EMC requirements.
EMC compatibility and motor cable length
To comply with the European EMC Directive (standard EN 61800-3), use the
following maximum motor cable lengths at 4 kHz switching frequency. See the
table below.
Maximum motor cable length, 4 kHzFrame size
ftm
EMC limits for Category C3
1)
Standard drive with an internal EMC filter.
See notes 3 and 4.
10030R0
10030R1
10030R2
492150R3
154 Technical data