Operational functionality and motor cable lengthMaximum recommended
motor cable length The drive is designed to operate with optimum performance
with the following maximum motor cable lengths.
Maximum motor cable length, 4 kHzFrame size
Vector controlScalar control
ftmftm
Standard drive, without external options
330100330100R0*
330100330100R1*
330100330100R2*
990300990300R3
990300990300R4
990300990300R5
990300990300R6
990300990300R7
990300990300R8
3AXD10000561047.xls A
Note 1: In multi-motor system, the sum of all motor cable lengths
shall not exceed that given in the following table.
Note 2: Longer cables cause a motor voltage decrease which
limits the available motor power. The decrease in voltage de-
pends on the motor cable length and characteristics. A sine filter
(optional) at the drive output can also cause a decrease in
voltage. For more information, consult your local ABB Service
representative (http://new.abb.com/channel-partners/search).
*)Conducted and radiated emissions of these motor cable
lengths do not comply with EMC requirements.
■
EMC compatibility and motor cable length
To comply with the European EMC Directive (standard EN 61800-3), use the
following maximum motor cable lengths at 4 kHz switching frequency. See the
table below.
Maximum motor cable length, 4 kHzFrame size
ftm
EMC limits for Category C3
1)
Standard drive with an internal EMC filter.
See notes 3 and 4.
10030R0
10030R1
10030R2
492150R3