EasyManua.ls Logo

ABB ACS560 - Input Power Cable; Notes

ABB ACS560
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PE
2b
3. Connect the motor cable as follows:
If the power cable is temporarily removed from the grounding shelf, connect the
motor and input power cables except the 360° grounding, and then reinstall the
grounding shelf.
Ground the shield 360° by tightening the clamp of the power cable grounding
shelf onto the stripped part of the cable (4a).
Connect the twisted shield of the cable to the grounding terminal (4b).
Connect the phase conductors of the cable to the T1/U, T2/V and T3/W
terminals.
Tighten the screws to the torque given below:
R4R3Frame size
lbf·ftN·mlbf·ftN·m
3.04.01.8…3.32.5…4.5T1/U. T2/V. T3/W.
4a
4b
4c
Notes:
The screws are of different length. Install them at correct locations.
After reinstalling the grounding shelf, you can make the 360° grounding for
the cables.
Input power cable
4. Prepare the ends of the cable as illustrated in the figure.
96 Electrical installation