Note: The voltage at the STO input terminals of the drive must be at least 13 V DC
to be interpreted as “1”.
The pulse tolerance of the input channels is 1 ms.
Grounding of protective shields
Ground the shield in the cabling between the activation switch and the control
unit at the control unit only.
Ground the shield in the cabling between two control units at one control unit
only.
198 The Safe torque off function