EasyManua.ls Logo

ABB ACS560 - Ground-To-Phase Varistor

ABB ACS560
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Ground-to-phase varistor
The ground-to-phase varistor is not suitable for use on an IT (ungrounded) system.
Disconnect the ground-to-phase varistor before connecting the drive to the supply
network. Check the table below.
WARNING! WARNING!
Do not install the drive with the ground-to-phase varistor connected on an
IT system (an ungrounded power system or a high-resistance-grounded
[over 30 ohms] power system), otherwise the varistor circuit can be damaged.
Check from the table below if you have to disconnect the EMC filter (EMC) or
ground-to-phase varistor (VAR).
IT systems (un-
grounded or
high-resistance
grounded [>30
ohms])
3
Corner groun-
ded TN systems
2
Symmetrically
grounded TN
systems (TN-S
systems)
1
Ground- to-
phase varis-
tor
(VAR)
EMC filter
(EMC)
Frame
sizes
DisconnectDisconnectDo not discon-
nect
-EMC (1
screw)
R0…R3
DisconnectDo not discon-
nect
Do not discon-
nect
VAR (1
screw)
-
DisconnectFrames R4 and
R5 cannot be
used in corner
grounded TN
systems.
Do not discon-
nect
-EMC (2
screws)
R4…R5
DisconnectDo not discon-
nect
VAR (1
screw)
-
DisconnectDisconnectDo not discon-
nect
-EMC (2
screws)
R6…R8
DisconnectDo not discon-
nect
Do not discon-
nect
VAR(1 screw)-
1 2 3
Drive
PE
N
L3
L2
L1
Drive Drive
PE
L3
L2
L1
L3
L2
L1
86 Electrical installation

Table of Contents

Other manuals for ABB ACS560

Related product manuals