Motor power supply selection (drive or direct-on-line)S40
Start when the motor is connected direct-on-lineS41
Stop when the motor is connected direct-on-lineS42
DriveU1
Switching the motor power supply from drive to direct-on-line
1. Stop the drive and the motor with the drive control panel (drive in local control
mode) or with the external stop signal (drive in remote control mode).
2. Open the main contactor of the drive with S11.
3. Switch the motor power supply from the drive to direct-on-line with S40.
4. Wait for 10 seconds to allow the motor magnetization to die away.
5. Start the motor with S41.
Switching the motor power supply from direct-on-line to drive
1. Stop the motor with S42.
2. Switch the motor power supply from direct-on-line to the drive with S40.
3. Close the main contactor of the drive with switch S11 (-> turn to position ST
for two seconds and leave at position 1).
4. Start the drive and the motor with the drive control panel (drive in local control
mode) or with the external start signal (drive in remote control mode).
Protecting the contacts of relay outputs
Inductive loads (relays, contactors, motors) cause voltage transients when switched
off.
It is highly recommended that inductive loads are equipped with noise attenuating
circuits (varistors, RC filters [AC] or diodes [DC]) in order to minimize the EMC
emission at switch-off. If not suppressed, the disturbances may connect
capacitively or inductively to other conductors in the control cable and form a risk
of malfunction in other parts of the system.
Install the protective component as close to the inductive load as possible. Do not
install protective components at the relay outputs.