Maximum motor cable length, 4 kHzFrame size
ftm
492150R4
492150R5
492150R6
492150R7
492150R8
1)
See the terms in section Definitions (page 168). Applicable for frames R4...R8. Frames R0...R2 require
external EMC filter to meet the category 2 standards.
Note 1: Radiated emissions are according to C3 with an internal EMC filter.
Note 2: The internal EMC filter must be connected.
Note 3: Radiated and conducted emissions are according to category C3 with an
internal filter and these cable lengths.
Note 4: Categories C1 and C2 meet requirements for connecting equipment to the
public low-voltage networks.
Brake resistor connection data for frames R0…R3
The brake resistor output is conditionally short-circuit proof
by IEC/EN 61800-5-1 and UL 508C. Rated conditional short-cir-
cuit current as defined in IEC 6439-1.
Short-circuit protection
(IEC/EN 61800-5-1, IEC
6439-1)
Control connection data
Maximum power:External power supply
Frames size R0…R2: (Without external power supply)
Frames size R3...R5: 25 W, 1.04 A at 24 V AC/DC ±10%
Frames size R6…R8 : 36W, 1.50A (24V AC/DC±10%, standard
configuration)
Supplied from an external power supply through option module
CMOD-01 with frames R3…R5. With frames R6…R8 no options
are needed.
Total load capacity of the outputs is 6.0W (250mA/24V) minus
the power taken by the option modules installed on the board.
+24 V DC output
(Term. 10)
Technical data 155