Note 2: Fuses with higher current rating than the recommended ones must not
be used.
Note 3: Fuses from other manufacturers can be used if they meet the ratings and
the melting curve of the fuse does not exceed the melting curve of the fuse
mentioned in the table.
■
uR and aR fuse
uR and aRInput cur-
rent
Minimum
short cir-
cuit cur-
rent
1)
Drive type
ACS560
IEC
60269
size
Bussmann
designation
type
Rated
voltage
I
2
tRated
current
I
N
VA
2
sAAA
3 phases U
N
= 400 V (380...480 V)
00170M2694690125254.24802A6-4
00170M2694690125255.34803A3-4
00170M2695690275326.48004A0-4
00170M2695690275329.08005A6-4
00170M26966904904011.512807A2-4
00170M269669010004015.012809A4-4
00170M269769018005020.220012A6-4
00170M269869036006327.2256017A-4
00170M269969014508040.0400025A-4
000170M156569014506332.0170033A-4
000170M156569025506338.0170039A-4
000170M156669046508045.0280046A-4
1170M1567690850010062.0380062A-4
000170M15686901600012573.0480073A-4
1170M15696901500016088.0480088A-4
1170M381569028500200106.0700106A-4
1170M381669046500250145.01000145A-4
1170M381769068500315169.01280169A-4
1170M3818690105000350206.01520206A-4
2170M5809690145000450246.02050246A-4
2170M5810690275000500293.02200293A-4
1)
minimum short-circuit current of the device
3AXD10000561047.xls A
144 Technical data