8. Connect the twisted shield to the grounding terminal (6b) and the conductors
to the UDC+/R+ and R- terminals (6c).
6a
6b
6c
9. Tighten the screws to the torque given below.
R2R0…R1Frame size
lbf·ftN·mlbf·ftN·m
0.9…1.11.2…1.50.40.5…0.6UDC+/R+, R-
Finalization
10. Ground the motor cable shield at the motor end. For minimum radio frequency
interference, ground the motor cable shield 360° at the lead-through of the motor
terminal box.